MAVOWATT 270-400 | MAVOWATT 240 | MAVOWATT 30 | MAVOWATT 270 | MAVOWATT 230 | MAVOWATT 210 | |
---|---|---|---|---|---|---|
New | ||||||
Item number | M820K | M820B | M817A | M820C | M820A | M840B |
Product details page | Details | Details | Details | Details | Details | Details |
Indication | Graphic | Graphic | Digital | Graphic | Graphic | None |
Number of voltage input channels | 4 | 4 | 4 | 4 | 4 | 4 |
Number of current input channels | 4 | 4 | 4 | 4 | 4 | 4 |
Current measurement | With current clamp meter/clamp adapter | With current clamp meter/clamp adapter | With current clamp meter/clamp adapter | With current clamp meter/clamp adapter | With current clamp meter/clamp adapter | With current clamp meter/clamp adapter |
Top arbour measurement | x | x | x | x | x | x |
Power factor | x | x | x | x | x | x |
Effective power | x | x | x | x | x | x |
Reactive power | x | x | x | x | x | x |
Apparent power | x | x | x | x | x | x |
Step angle (cos phi) | x | x | x | x | x | x |
Power/work | x | x | x | x | x | |
Interface | x | x | x | x | x | x |
Measured value memory | x | x | x | x | x | x |
Current supply | 220V/accu | 220V/accu | 220V/accu | 220V/accu | 220V/accu | Accumulator/mains |
Voltage measurement range/AC direct | 0V - 1000V | 0V - 1000V | 0V - 1000V | 0V - 1000V | ||
Communication |
Ethernet Wi-Fi Bluetooth USB VNC for full remote control of the instrument Apple and Android apps for acquisition and alarm generation GPS time synch * (see comment) |
Ethernet Wi-Fi Bluetooth USB VNC for full remote control of the instrument Apple and Android apps for acquisition and alarm generation GPS time synch * (see comment) |
Ethernet Wi-Fi Bluetooth USB VNC for full remote control of the instrument Apple and Android apps for acquisition and alarm generation GPS time synch * (see comment) |
Ethernet Bluetooth VNC for full remote control of the instrument Apple and Android apps for acquisition and alarm generation GPS time synch * (see comment) |
Ethernet USB |
|
Input |
Differential, voltage channels for current sensors, 0.1 to 6000A (AC/DC) with supply voltage for flexible current sensors Differential, voltage channels, 0 to 1000 V AC/DC |
Differential, voltage channels for current sensors, 0.1 to 6000A (AC/DC) with supply voltage for flexible current sensors Differential, voltage channels, 0 to 1000 V AC/DC |
Differential, voltage channels for current sensors, 0.1 to 6000A (AC/DC) with supply voltage for flexible current sensors Differential, voltage channels, 0 to 1000 V AC/DC |
Differential, voltage channels for current sensors, 0.1 to 6000A (AC/DC) with supply voltage for flexible current sensors Differential, voltage channels, 0 to 1000 V AC/DC |
||
Measurement |
1000V CAT III, 600V CAT IV IEC 61000-4-30:2008, class A with certificate Sampling rate: 512 values/period/channel for U & I U-I dips and swells Transients as of 332/40µs (60/50 Hz) Transients as of 1µs Power demand and energy consumption IEEE 1459, advanced energy Harmonics and interharmonics U (127), I (63) EN 50160, edition 3 400 Hz monitoring |
1000V CAT III, 600V CAT IV IEC 61000-4-30:2008, class A with certificate Sampling rate: 512 values/period/channel for U & I U-I dips and swells Transients as of 332/40µs (60/50 Hz) Power demand and energy consumption IEEE 1459, advanced energy Harmonics and interharmonics U (127), I (63) EN 50160, edition 3 |
1000V CAT III, 600V CAT IV IEC 61000-4-30:2008, class A with certificate Sampling rate: 512 values/period/channel for U & I U-I dips and swells Transients as of 332/40µs (60/50 Hz) Transients as of 1µs Power demand and energy consumption IEEE 1459, advanced energy Harmonics and interharmonics U (127), I (63) EN 50160, edition 3 |
1000V CAT III, 600V CAT IV IEC 61000-4-30:2008, class A with certificate Sampling rate: 512 values/period/channel for U & I U-I dips and swells Transients as of 332/40µs (60/50 Hz) Power demand and energy consumption Harmonics and interharmonics U (127), I (63) EN 50160, edition 3 |
||
Answer modules |
Motor status Voltage dip direction Switching of compensation capacitors |
Motor status Voltage dip direction Switching of compensation capacitors |
Motor status Voltage dip direction Switching of compensation capacitors |
Motor status | ||
Set-ups |
Number of transient triggers Automatic setups for power quality, power demand and energy consumption Setup wizard Max. pre/post-trigger periods Monitoring operating modes |
Number of transient triggers Automatic setups for power quality, power demand and energy consumption Setup wizard Max. pre/post-trigger periods Monitoring operating modes |
Number of transient triggers Automatic setups for power quality, power demand and energy consumption Setup wizard Max. pre/post-trigger periods Monitoring operating modes |
Number of transient triggers Automatic setups for power quality, power demand and energy consumption Monitoring operating modes Setup wizard Max. pre/post-trigger periods |
||
Max. pre-/post-trigger periods | 100000 | 100000 | 100000 | 100 | ||
Frequency measuring range | 16 2/3, 50 to 60 Hz | 16 2/3, 50 to 60 Hz | ||||
Voltage measuring range/AC direct |