• Gossen Metrawatt
  • Camille Bauer

Characteristic Values

MAVOWATT 270-400 MAVOWATT 240 MAVOWATT 30 MAVOWATT 270 MAVOWATT 230 MAVOWATT 210
New
Item number M820K M820B M817A M820C M820A M840B
Product details page Details Details Details Details Details Details
Indication Graphic Graphic Digital Graphic Graphic None
Number of voltage input channels 4 4 4 4 4 4
Number of current input channels 4 4 4 4 4 4
Current measurement With current clamp meter/clamp adapter With current clamp meter/clamp adapter With current clamp meter/clamp adapter With current clamp meter/clamp adapter With current clamp meter/clamp adapter With current clamp meter/clamp adapter
Top arbour measurement x x x x x x
Power factor x x x x x x
Effective power x x x x x x
Reactive power x x x x x x
Apparent power x x x x x x
Step angle (cos phi) x x x x x x
Power/work x x x x x
Interface x x x x x x
Measured value memory x x x x x x
Current supply 220V/accu 220V/accu 220V/accu 220V/accu 220V/accu Accumulator/mains
Voltage measurement range/AC direct 0V - 1000V 0V - 1000V 0V - 1000V 0V - 1000V
Communication Ethernet
Wi-Fi
Bluetooth
USB
VNC for full remote control of the instrument
Apple and Android apps for acquisition and alarm generation
GPS time synch * (see comment)
Ethernet
Wi-Fi
Bluetooth
USB
VNC for full remote control of the instrument
Apple and Android apps for acquisition and alarm generation
GPS time synch * (see comment)
Ethernet
Wi-Fi
Bluetooth
USB
VNC for full remote control of the instrument
Apple and Android apps for acquisition and alarm generation
GPS time synch * (see comment)
Ethernet
Bluetooth
VNC for full remote control of the instrument
Apple and Android apps for acquisition and alarm generation
GPS time synch * (see comment)
Ethernet
USB
Input Differential, voltage channels for current sensors, 0.1 to 6000A (AC/DC) with supply voltage for flexible current sensors
Differential, voltage channels, 0 to 1000 V AC/DC
Differential, voltage channels for current sensors, 0.1 to 6000A (AC/DC) with supply voltage for flexible current sensors
Differential, voltage channels, 0 to 1000 V AC/DC
Differential, voltage channels for current sensors, 0.1 to 6000A (AC/DC) with supply voltage for flexible current sensors
Differential, voltage channels, 0 to 1000 V AC/DC
Differential, voltage channels for current sensors, 0.1 to 6000A (AC/DC) with supply voltage for flexible current sensors
Differential, voltage channels, 0 to 1000 V AC/DC
Measurement 1000V CAT III, 600V CAT IV
IEC 61000-4-30:2008, class A with certificate
Sampling rate: 512 values/period/channel for U & I
U-I dips and swells
Transients as of 332/40µs (60/50 Hz)
Transients as of 1µs
Power demand and energy consumption
IEEE 1459, advanced energy
Harmonics and interharmonics U (127), I (63)
EN 50160, edition 3
400 Hz monitoring
1000V CAT III, 600V CAT IV
IEC 61000-4-30:2008, class A with certificate
Sampling rate: 512 values/period/channel for U & I
U-I dips and swells
Transients as of 332/40µs (60/50 Hz)
Power demand and energy consumption
IEEE 1459, advanced energy
Harmonics and interharmonics U (127), I (63)
EN 50160, edition 3
1000V CAT III, 600V CAT IV
IEC 61000-4-30:2008, class A with certificate
Sampling rate: 512 values/period/channel for U & I
U-I dips and swells
Transients as of 332/40µs (60/50 Hz)
Transients as of 1µs
Power demand and energy consumption
IEEE 1459, advanced energy
Harmonics and interharmonics U (127), I (63)
EN 50160, edition 3
1000V CAT III, 600V CAT IV
IEC 61000-4-30:2008, class A with certificate
Sampling rate: 512 values/period/channel for U & I
U-I dips and swells
Transients as of 332/40µs (60/50 Hz)
Power demand and energy consumption
Harmonics and interharmonics U (127), I (63)
EN 50160, edition 3
Answer modules Motor status
Voltage dip direction
Switching of compensation capacitors
Motor status
Voltage dip direction
Switching of compensation capacitors
Motor status
Voltage dip direction
Switching of compensation capacitors
Motor status
Set-ups Number of transient triggers
Automatic setups for power quality, power demand and energy consumption
Setup wizard
Max. pre/post-trigger periods
Monitoring operating modes
Number of transient triggers
Automatic setups for power quality, power demand and energy consumption
Setup wizard
Max. pre/post-trigger periods
Monitoring operating modes
Number of transient triggers
Automatic setups for power quality, power demand and energy consumption
Setup wizard
Max. pre/post-trigger periods
Monitoring operating modes
Number of transient triggers
Automatic setups for power quality, power demand and energy consumption
Monitoring operating modes
Setup wizard
Max. pre/post-trigger periods
Max. pre-/post-trigger periods 100000 100000 100000 100
Frequency measuring range 16 2/3, 50 to 60 Hz 16 2/3, 50 to 60 Hz
Voltage measuring range/AC direct