No, this is not possible! Resolution depends upon the selected current and voltage transformers, and is thus independent of the actual measured quantity.
An overview is provided below:
Voltage display relative to primary phase conductor voltage
Primary Phase Conductor Voltage |
Display | Quantity via Interface |
||
---|---|---|---|---|
> 60 kV > 6 kV 700 V 100 V |
...750 kV ...60 kV ...6 kV ...600 V |
xxx.x kV xx.xx kV xxxx V xxx.x V |
dim.U = | 2 1 0 -1 |
Current display relative to primary current
Primary Current | Display | Quantity via Interface |
||
---|---|---|---|---|
> 60 kA > 6 kA > 600 A 65 A 10 A 1 A |
...150 kA ...60 kA ...6 kA ...600 A ...60 A ...5 A |
xxx.x kA xx.xx kA xxxx A xxx.x A xx.xx A x.xxx A |
dim.I = | 2 1 0 -1 -2 -3 |
Power and energy display relative to the product of
primary phase voltage and primary current
Primary Power (energy) |
Display | Quantity via Interface |
||
---|---|---|---|---|
> 36 GW > 3.6 GW > 360 MW > 36 MW > 3.6 MW > 360 kW > 36 kW > 3.6 kW 400 W 100 W |
... 112.5 GW ... 36 GW ... 3.6 GW ... 360 MW ... 36 MW ... 3.6 MW ... 360 kW ... 36 kW ... 3.6 kW ... 300 W |
xxx.x MkW xx.xx MkW xxxx MW xxx.x MW xx.xx MW xxxx kW xxx.x kW xx.xx kW xxxx W xxx.x W |
dim.P = | 8 7 6 5 4 3 2 1 0 -1 |